Harmonic Parallel Resonance Issues in Power Factor Correction Capacitors and Mitigation via 6% Series Reactors
·2026.11.18 14:12
Key point
Applying a 6% series reactor shifts the circuit to inductive behavior at the 5th harmonic and above, thereby preventing resonance.
Details
- Power factor correction capacitors experience current amplification by several dozen times due to parallel resonance in harmonic environments, leading to burnout and degradation from self-induced current and voltage increases.
- When a 6% series reactor is applied, the circuit transitions to inductive behavior at the 5th harmonic (300 Hz) and above, failing to meet the conditions for parallel resonance.
- The effective current of the capacitor increases as the root sum square of the fundamental and harmonic currents, while terminal voltage rise causes breakdown of internal inter-electrode and ground insulation.
- In accordance with KS/IEC standards, designs for low-voltage systems with reactors must ensure the allowable current is below 120% and the allowable overvoltage is within 110%.
- For AIDC power receiving equipment, it is necessary to combine a 6% series reactor, select a rated current at least 1.3 times the fundamental current, and consider combining an Active Power Filter (APF) if harmonic THD is high.