Principles of Data Center Fire Protection Systems for Battery Thermal Runaway Response and Service Continuity
·2026.10.27 09:55
Key point
Data center fire protection systems are availability infrastructure designed to address battery thermal runaway and ensure service continuity.
Details
- Data center fire protection is not merely a legal obligation but an availability infrastructure, serving as the last line of defense against service outages caused by battery thermal runaway and power failures.
- In the 2022 Pango and 2025 Daejeon fire incidents, service interruptions caused by power cutoffs and thermal runaway resulted in greater damage than flame suppression efforts.
- Server rooms apply aspiration smoke detection (ASD), gas-based extinguishing, and pre-action sprinklers to avoid water damage, while battery rooms are trending toward separation by fire-resistant partitions and the concurrent use of water-based systems.
- Gas-based extinguishing allows for restart due to the absence of residue but has limitations in suppressing thermal runaway, leading to the adoption of next-generation technologies such as Water Mist and the transition to LFP batteries.
- During construction, fire compartment fire resistance, airtightness of protection zones (door fan testing), and dual verification using cross-circuit (AND) logic to prevent false alarms are essential.
- Alongside statutory inspections, decision-making training on 'when to cut power' and the establishment of redundancy systems are the core of actual fire response.