How Data Center Cooling Towers Reject Heat by Evaporating About 1% of Water, and How to Operate Them
Key point
Data center cooling towers release heat from cooling water into the atmosphere by evaporating about 1% of the water.
Details
- Data center cooling towers release into the atmosphere the heat absorbed from servers, as about 1% of the water evaporates and removes heat from the remaining water.
- Open-circuit towers are widely used at large data centers because the cooling water comes into direct contact with air, making them efficient and less expensive to install, but water quality must be managed.
- In closed-circuit towers, cooling water inside copper coils is isolated from outside air and therefore does not become contaminated, making them suitable for precision processes or environments where piping for expensive equipment must be protected.
- Variable-frequency drives (VFDs) adjust fan speed according to the outdoor temperature. In winter, they save electricity by stopping the chillers and using free cooling, in which water cooled by the cooling tower is used for cooling.
Performance and Installation
- Cooling Range is the difference between the water temperatures at the cooling tower inlet and outlet, while Cooling Approach is the difference between the outlet water temperature and the ambient wet-bulb temperature; a smaller value indicates higher heat-exchange efficiency.
- An example involving the installation of 13 large cooling towers with a capacity of 9,100 CRT requires a rooftop structural review, crane lifting routes, leveling of the base frames, and pipe welding.
White Plume and Water Quality Management
- Cooling towers designed to reduce white plumes use a dry heat exchanger to warm humid air before discharge, lowering its relative humidity and suppressing the formation of white water vapor.
- As water evaporates and minerals become concentrated, scale and slime can interfere with heat exchange and corrode piping, so operators manage water testing, blowdown, and the addition of water-treatment chemicals.